Circuit breaker size for 10kw heat strip
WebJan 29, 2012 · My guess is that, if it is in fact a 15 kW system (and it may be, with a heat pump of that size), it has a 10 kW heat strip and a 5 kW strip, perhaps staged in some fashion. The 10 kW strip would be on the 60A breaker, and probably everything else in the air handler -- the 5 kW strip, the blower, and the low voltage -- are on the 30A breaker.
Circuit breaker size for 10kw heat strip
Did you know?
WebJan 17, 2024 · Circuit Breaker Requirements Based On Unit Tonnage It is standard to measure air conditioner and heat pump size based on tonnage. When choosing a unit for your home, you’ll often see ACs and heat … WebJan 19, 2024 · 10 kW Heat Strip Breaker Size. The breaker size for a 10kW heat strip would typically be around 60 amps, as the maximum fuse breaker for this type of device is …
WebFeb 25, 2016 · #1 So When sizing Conductors for 15kw heat with a 3.9A Blower motor. You Have 15000/240=62.5A + 3.9A = 66.4A x 125%= 83A Conductor is 83A = #4 Thhn OCP is 83A so Code says if not a standard size fuse you need to go up to next standard size. (240.4B) 240.6A) With all that said is it all right to run a #4THHN and install 90A Fuses. WebNov 3, 2024 · How many amps is a 10kw heat strip? 240volts X 42amps = 10kw so you should be good to go. If your wire is labeled 55amps,55 is the max it should be for but #4 al is normally 65 amp. What size breaker do I need for a 15 kW heater? 15kw is better than 60 Amps. If you are positive that is indeed #4 cable…. you must use a sub panel.
WebExample 1: Which size circuit breaker is needed for 6.5kW, three phase 480V load? Solution: Power in Three Phase: P = V x I x √3 Current: P / V x √3 I = 6.5kW / (480V x 1.732) … (√3 = 1.732) I = 6.5kW / 831.36 I = 7.82A The recommended size of circuit breaker is 1.25 x 7.82A = 9.77A The next closest standard of circuit breaker is 10A. WebMar 3, 2013 · The 10kw heat strip called for a 60amp circuit breaker and I have a 50amp stab-loc breaker in a 200amp Federal Pacific Electric panel from the mid 1960s when the house was built. The tech installed the 10kw for a temporary heat source and came back the next day and installed the 7kw heat strip.
WebNov 10, 2009 · The 10kW needed one 60 amp breaker. The 15kW needed one 60 amp breaker plus one 30 amp breaker. I recall one option that our installer proposed was using a (a few actually) mini breaker where 2 circuits could use one breaker slot but still have two breakers built into the one mini breaker.
WebJan 19, 2024 · 10 kW Heat Strip Breaker Size. The breaker size for a 10kW heat strip would typically be around 60 amps, as the maximum fuse breaker for this type of device is typically 60 amps. This is based on the heating capacity of 30,001 BTU/H to 35,000 BTU/H and the voltage of 208V/230V. ... It is important to consider the other electrical loads that ... finley palm motor innWebNov 5, 2009 · 10 kW at 220v will use 45.45 Amps. I'd recommend a 60A circuit, with a 60A breaker, but the heater or electric furnace should have "maximum fuse amps" rated on its nameplate. Above all,... finley pain clinic dr millerWebNov 13, 2024 · I am now going to be installing a disconnect and Circuit Breaker (CB) for a 15KW heat strip (heat strip only, no other load). Previous electrician ran a 2 cdr 4 awg 1 cdr 6awg NM copper wire for this install. The heat strip is actually 14,400 watts 208/230 volt. I calculated the CB as 14,400/240 = 60A x 1.25 = 75A so I am using an 80A breaker. eso how to raise thief guild skillWebDec 10, 2024 · 3. Multiply the value for current by 125 percent to determine the size of the breaker you need for the heater. A 1500-watt heater on a 120-volt circuit thus needs a breaker of 15.6 amps. Because a ... finley packers injuryWebNov 5, 2009 · 10 kW at 220v will use 45.45 Amps. I'd recommend a 60A circuit, with a 60A breaker, but the heater or electric furnace should have "maximum fuse amps" rated on … finley paint and body lanett alWebHeat Strip Size: 10 kW: Max Overcurrent Protection: 60 amps: Primary Heating Capacity: 30,001 - 35,000 BTU: Product Height (in) 6.5: Product Length (in) 13.25: Product Width … eso how to play with friendsWeb10 Kw at 240 volts is 41.66 amps. 125% of this rating is 52 amps so the correct circuit breaker size is 60 amps and the disconnect will also be 60 amps. Wire size will depend on the length of run and the type of wire Sir Sparks : finley pain clinic